Advanced Instruments Co.,Limited

Advanced Instruments Co.,Limited To Be Advanced in Quality and Service!

Manufacturer from China
Verified Supplier
6 Years
Home / Products / Electrical Test Instrument /

Electrical Three Phase Secondary Current Injection Kit Relay Protection Test Set

Contact Now
Advanced Instruments Co.,Limited
Visit Website
City:changsha
Province/State:hunan
Country/Region:china
Contact Person:MrsSandy
Contact Now

Electrical Three Phase Secondary Current Injection Kit Relay Protection Test Set

Ask Latest Price
Video Channel
Brand Name :AI
Model Number :RPT-3
Certification :ISO
Place of Origin :China
MOQ :1 Set Three Phase Secondary Current Injection Kit
Price :Negotiable
Payment Terms :T/T, Western Union, L/C
Supply Ability :1000 sets per month
Delivery Time :15 days
Packaging Details :Three Phase Secondary Current Injection Kit packed in Plywood case
Power supply :AC 220V±10%
Display :LCD
3 Phase Current Output :0~120A
Max.power output :420VA
Warranty :1 Year
Keyword :Secondary Current Injection Kit
Phase current output :0~40A
Three parallel phase current output :120A
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Protection Relay Three Phase Secondary Current Injection Test Set

I.Introduction:

This secondary injection test kit is applied to test the relay unit in relay protection system. At the same time it could be considered as a universal three phase AC/DC voltage source or current source.

This relay protection tester is applied to test protection replay based on voltage and current operation.

The main function of 3 phase relay test set includes: calibration of voltage and current operation relays, secondary circuit inspection,trip value of circuit breaker test, switch on and off time measurement of circuit breaker and so on.

This secondary injection kit is a low cost, simple operation and reliable performance device for secondary circuit test.

II.Functions

1) AC current and voltage based protection relay unit test

2) DC current and voltage based protection relay unit test

3) Frequency protection relay unit test

4) Harmonic protection relay unit test

5) Differential protection relay unit test

6) Zero-sequence protection relay unit test

7) Distance protection relay unit test

8) Power system network fault simulation

III.Specifications:

No. Items Specifications
Alternating Current(AC) output
1 Output accuracy 0.5 magnitude
2 Phase current output (effective value) 0~40A
3 Three parallel phase current output (effective value) 0~120A
4 Phase current value with long time under permission (effective value) 10A
5 Phase current maximum power output 420VA
6 Three parallel phase current maximum power output 900VA
7 Three parallel phase current maximum work time 10s
8 Frequency range (base wave) 20~1000Hz
9 Harmonic frequency number 1~20 time
Direct Current(DC) output
1 Output accuracy 0.5magnitude
2 Current output

0 ~ ± 10 A/each phase

0 ~ ± 30 A/every three parallel

3 Maximum output of load voltage 20v
Alternating Voltage output
1 Output accuracy 0.5magnitude
2 Phase voltage output (RMS) 0 ~ 120v
3 Line voltage output (RMS) 0 ~ 240v
4 Phase voltage/line voltage power output 80VA/100VA
5 Frequency range (base wave) 20 ~ 1000Hz
6 Harmonic frequency number 1 ~ 20 times
Direct voltage output
1 Output accuracy 0.5magnitude
2 Phase voltage output amplitude 0 ~ +160v
3 Line voltage output amplitude 0 ~ + 320v
4 Phase voltage/line voltage power output 70VA/140VA
The switch quantity and time measurement
1 Switch parameters input

7 ways;

Empty contact: 1~20mA, 24v

Power contact access: “0”:0~ +6V;

“1”:+11 V~ +250V

2 Switch parameters output 2 couples DC:220V/0.2A; AC:220V/0.5A
3 Time measurement Measuring range: 0.1ms ~ 9999s / 0.1ms

Spare of Three Phase Secondary Injection Test Kit

Electrical Three Phase Secondary Current Injection Kit Relay Protection Test Set