Advanced Instruments Co.,Limited

Advanced Instruments Co.,Limited To Be Advanced in Quality and Service!

Manufacturer from China
Verified Supplier
6 Years
Home / Products / Electrical Test Instrument /

Lightweight Transformer Hipot Test Machine AC DC High Voltage Dry Type

Contact Now
Advanced Instruments Co.,Limited
Visit Website
City:changsha
Province/State:hunan
Country/Region:china
Contact Person:MrsSandy
Contact Now

Lightweight Transformer Hipot Test Machine AC DC High Voltage Dry Type

Ask Latest Price
Video Channel
Brand Name :AI
Model Number :DHP
Certification :ISO
Place of Origin :China
MOQ :1 Set AC DC Hipot
Price :Negotiable
Payment Terms :T/T, Western Union, L/C
Supply Ability :1000 sets per month
Delivery Time :15 days
Packaging Details :AC DC Hipot packed in Plywooe case
Power supply :AC220V±10%, 50Hz/60Hz
Type :Dry transformer
Voltage output :50KV/100KV
Keyword :AC DC Hipot,Dry Type Test Transformer
Output capacity :5~150KVA
Warranty :1 Year
Purpose :insulation test of high voltage equipment
Operation :Manual
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

AC and DC High Voltage Dry Type Test Transformer

I. Introduction:

Dry Type Test Transformer AC DC Hipot Tester is applied in power system for insulation test of high voltage equipment.

The typical application of the HIPOT tester is as follow:

  • Power Transformer AC high voltage withstand test

  • Circuit Breaker AC high voltage withstand test

  • High voltage motors high voltage withstand test

  • Voltage/current transformer high voltage withstand test

  • High voltage power source for calibration of high voltage meter

II. Specifications:

  • Please confirm the right model before order. The main parameters include input voltage, maximum output voltage and capacity.

  • The parameters in this table are response for HV tes transformer only and we will match the main control box according to the capacity and input voltage you need.

Model

Max output capacity

(KVA)

Max high voltage

output (KV)

Max current

in hv circuit

(MA)

Voltage current

input of voltage

booster(V)

Voltage current

input of voltage

booster (A)

Ratio
DHP (D)-5/50 5 50 100 200 25 500
DHP (D) -10/50 10 50 200 220/380 50/26 500
DHP (D) -20/50 20 50 400 380 53 500
DHP (D) -30/50 30 50 600 380 79 500
DHP (D)-40/50 40 50 800 380 105 500
DHP (D) -50/50 50 50 1000 380 132 500
DHP (D) -5/100 5 100 50 200 25 1000
DHP (D) -10/100 10 100 100 200/380 50/26 1000
DHP (D)-20/100 20 100 200 380 53 1000
DHP (D)-30/100 30 100 300 380 79 1000
DHP (D) -40/100 40 100 400 380 105 1000
DHP (D)-50/100 50 100 500 380 132 1000
DHP (D)-100/100 100 100 100 500 263 1000
DHP (D) -150/100 150 100 1500 500 300 1000

Note:The capacity and maximum voltage output could be customized according to the requirements if you can not find the right one in this table;

The weight listed in the table is HV test transformer only,and it does not include the weight of main control box. Please confirm the total weight of AC or AD/DC hipot tester with our sales before order.

Picture of AC DC Dry Type Hipot Test Transformer

Lightweight Transformer Hipot Test Machine AC DC High Voltage Dry Type

Lightweight Transformer Hipot Test Machine AC DC High Voltage Dry Type

Inquiry Cart 0