Advanced Instruments Co.,Limited

Advanced Instruments Co.,Limited To Be Advanced in Quality and Service!

Manufacturer from China
Verified Supplier
6 Years
Home / Products / Electrical Test Instrument /

Electrical Test Instrument for Transformer Winding Deformation Displacement Test

Contact Now
Advanced Instruments Co.,Limited
Visit Website
City:changsha
Province/State:hunan
Country/Region:china
Contact Person:MrsSandy
Contact Now

Electrical Test Instrument for Transformer Winding Deformation Displacement Test

Ask Latest Price
Video Channel
Brand Name :AI
Model Number :SFRA-II
Certification :ISO
Place of Origin :China
MOQ :1 Set Transformer Winding Deformation Test Instrument
Price :Negotiable
Payment Terms :T/T, Western Union, L/C
Supply Ability :1000 sets per month
Delivery Time :15 days
Packaging Details :Transformer Winding Deformation Test Instrument packed in Plywood case
Power supply :AC220V±10%, 50Hz/60Hz
Display :LCD
Sweep modes :Linear sweep, Section sweep
Test range :(-100dB) - (+20dB)
Warranty :1 Year
Keyword :Transformer Winding Deformation Tester
Test standard :IEC60076-18-2012 and IEC60076-5-2006
Test object :transformer
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Transformer Winding Deformation Displacement Distortion Tester

I. Introduction:

Our company has designed the frequency response analyzer SFRA-II, which can use two methods to detect the deformation of the transformer at the same time. One is the sweep frequency response analysis method, the other is low-voltage short-circuit impedance method. Using two methods can effectively reduce incorrect judgments.

SFRA-II Transformer Winding Deformation Tester follows the national power industry standards DL / T911-2004 and DLT 1093-2008, and can be used for IEC60076-18-2012 and IEC60076-5-2006.

II.Main Features

1. Using the advanced technical of DDS;
2. Using the high speed and advanced microprocessor to design;
3. Using AD chip of 16 bits;
4. Transformer Winding Deformation Test Instrument adopts seven inch LCD touch screen of which the brightness can be adjusted;
5. With thermal printer of which the print thick can be adjusted;
6. It could store one hundred and twenty groups of FRA data, fifty groups of SCI data and thirty groups of SCI data, which could be read to current screen or upload to the PC;
7. With PC software using which we could upload data ,test, analyze data, print data, or create word document;
8. Transformer Winding Deformation Test Instrument uses USB2.0 to connect to the device;

III. Technical Specifications:

Sweep frequency response analysis

Two different sweep modes: Linear sweep, Section sweep
Linear sweep

10HZ-1MHZ interval 0.5KHZ 2000 dots

100HZ-2MHZ interval 0.5KHZ 2000 dots

10HZ-1MHZ interval 0.25KHZ 4000 dots(PC available)

100KHZ-2MHZ interval 0.25KHZ 4000 dots(PC available)

Frequency,interval,and scan dots can be set(PC available)

Section sweep

10HZ-100HZ interval 1HZ 90 dots

100HZ-1KHZ interval 5HZ 180 dots

1KHZ -10KHZ interval 50HZ 180 dots

10KHZ-100KHZ interval 0.2KHZ 450 dots

100KHZ –300KHZ interval 0.5KHZ 400 dots

300KHZ – 1000KHZ interval 1KHZ 700 dots

Test range (-100dB) - (+20dB)
Test accuracy (-80dB) - (+20dB)0.2dB (-100dB) - (-80dB)1.0dB
Frequency accuracy < 0.01%
Signal input impedance > 1M Ω
Signal output impedance 50 Ω
In-phase test repetition rate 99.5%

Short-circuit impedance and generator rotor AC impedance:

AC impedance 0~999.999Ω 0.2%±2 digits
AC voltage 0~600V 0.2%±2 digits
AC ampere 0~120A 0.2%±2 digits
Active power

cosφ>0.1 0.5%±2 digits

cosφ<0.1 1.0%±2 digits

Reactive power 0.2%±2 digits

Frequency 45~65HZ 0.1%

Electrical Test Instrument for Transformer Winding Deformation Displacement Test